Results: 35% baffle cut dropped pressure drop to 65 kPa (good) but U fell to 235 (bad). 20% baffle cut? Pressure drop: 110 kPa—unsafe for the diesel pump. She needed a different geometry entirely.

Better. U climbed to 250. But pressure drop on the shell side spiked—from 40 kPa to 95 kPa, exceeding the 70 kPa limit. Trade-off city. htri heat exchanger design

Elena reduced unsupported tube length by adding support plates. She increased tube wall thickness from 1.65 mm to 2.11 mm. HTRI’s vibration analysis tab recalculated: frequency ratio now 1.8 (safe above 1.2). Red warning turned yellow, then green. Results: 35% baffle cut dropped pressure drop to