Examples In Electrical Calculations | By Admiralty Pdf

Chief Electrician Arthur Gibbs wiped salt spray from his spectacles. Below decks, the newly installed gyrocompass was humming erratically. The Captain wanted answers. Gibbs reached for the worn, blue-covered manual: — his bible for shipboard power systems. Example 1: Cable Sizing for a Deck Winch The forward mooring winch had been tripping its breaker. Gibbs suspected voltage drop. The winch motor drew 85 A at 110 V DC (common on older naval vessels). The cable run from the main switchboard to the winch was 45 meters of two-core armored cable.

Using the formula: [ R = \frac{V_{drop}}{I} = \frac{1.65}{85} \approx 0.0194\ \Omega ] examples in electrical calculations by admiralty pdf

The Admiralty tables listed nearest standard: copper cable. Installing that solved the tripping. Gibbs noted: “Always account for temperature rise — use 0.0204 Ω·mm²/m at 45°C for safety.” Example 2: Short-Circuit Calculation for a Searchlight A 3 kW searchlight (110 V) suddenly failed. A cable chafed against a bulkhead, causing a dead short. Gibbs needed to prove the protective fuse was correct. Chief Electrician Arthur Gibbs wiped salt spray from

Checking the fuse’s time-current curve (Admiralty Handbook, Plate 12), a 40 A fuse would clear 1285 A in ~0.01 seconds — safe. But the mechanical switch arced badly. Gibbs recommended adding a high-speed circuit breaker. Post-war, HMS Vigilant got new radar. The induction motor load (radar rotating aerial) had a power factor of 0.65 lagging . Apparent power S = 8 kVA, true power P = 5.2 kW. The generator ran hot. Gibbs reached for the worn, blue-covered manual: —

Then cable cross-section area (A): [ A = \frac{\rho \times L}{R} = \frac{0.0175 \times 45}{0.0194} \approx 40.6\ \text{mm}^2 ]

Fault current: (I_{short} = 110 / 0.0856 \approx 1285\ \text{A}).