For : | Parameter | Value | |-----------|-------| | Set | -18°C | | Hy | 2°C | | LS | -30°C | | US | -10°C | | dtE | 15°C | | MdF | 30 minutes | | idF | 8 hours | Conclusion The Dixell XW60LS is a reliable, flexible controller for commercial refrigeration. Mastering its parameter structure, wiring, and alarm handling allows technicians to optimize energy efficiency, protect compressors, and maintain precise temperature control. Always keep a copy of the official parameter list and use the Hot Key for rapid deployment across multiple units.
For specific OEM variations (e.g., XW60LS with different probe curves or custom passwords), consult the original equipment manufacturer’s supplement. Refer to Emerson/Copeland’s official XW60LS – ISTR 03/11 installation manual or contact technical support with the controller’s full model code and firmware version (visible during power-up). dixell xw60ls manual
| i1P | Function | |-------|-----------| | oP | Door switch – normal open | | cL | Door switch – normal closed | | EAL | External alarm (generic) | | bAL | Serious alarm (compressor stop) | | PAL | Pressure switch alarm | | dor | Door switch with fan cut-off and defrost inhibition | For : | Parameter | Value | |-----------|-------|